Loading...

Securitron XDT-12 Exit Delay Timer Board 12 VDC

£246.78 £205.65
SKU
XDT-12
  • This product is available to order. The lead time is normally 2 – 4 working days.
  • An accurate despatch date will be confirmed with you once order is received by our sales team (during office hours).
Free Delivery

Free Delivery on this product

Securitron XDT-12 Exit Delay Timer board only, 12 VDC. Three 5A SPDT relays, configurable nuisance and release delays via DIP switches. NFPA 101 compliant delayed egr

Securitron XDT-12 Exit Delay Timer for Delayed Egress Applications

The Securitron XDT-12 is a sophisticated, modular exit delay timer board designed for fail-safe environments requiring delayed egress functionality. Operating at 12 VDC, this board-only unit integrates with Securitron Magnalock electromagnetic locks, Touch Sense Bars and other switch-equipped initiating devices to create a code-compliant delayed egress system. It meets NFPA 101 Life Safety Code, BOCA, UBC, SBC and National Building Code of Canada requirements for Special Locking Arrangements.

The XDT-12 provides three independently configurable 5A SPDT relay outputs for lock control, remote alarm and local alarm functions. Nuisance delay and release times are digitally set using precise DIP switches, eliminating trial-and-error adjustment. External switches such as time clocks can put the timer into different operational modes when delayed exit is not required at all times, making it well suited to healthcare, retail and mixed-use environments.

Key Features

  • 12 VDC operation with 100 mA current draw
  • Three 5A SPDT relay outputs for lock control, remote alarm and local alarm
  • Configurable nuisance delay: disabled, 1, 2 or 3 seconds
  • Selectable release delay: 15 or 30 seconds via DIP switch
  • BOCA timed relocking mode with 30-second relock delay
  • Free egress mode for immediate release without alarm
  • Lockdown mode to prevent unauthorised egress
  • Bypass input for scheduled release or authorised 5-second timed entry and exit
  • Lock status reporting input for propped or forced door monitoring
  • Delay Control terminal keeps lock engaged after release delay expires
  • Low voltage sensing circuit releases lock at approximately 70 percent of nominal voltage
  • 4-position DIP switch for configuration
  • Includes MOV for inductive kickback protection — not needed with Securitron Magnalocks
  • Compatible with Securitron Touch Sense Bars, MK keyswitches, DT-7 time clocks and switch-equipped panic bars
  • Board-only format for flexible installation
  • MagnaCare lifetime replacement no-fault warranty

Technical Specifications

  • Voltage: 12 VDC (tolerance -10 percent to +20 percent)
  • Current draw: 100 mA maximum
  • Relay outputs: 3 x 5A SPDT
  • Nuisance delay options: disabled, 1 sec, 2 sec, 3 sec
  • Release delay options: 15 sec or 30 sec
  • Bypass off-delay: 5 seconds
  • Lock status delay: 5 seconds
  • Low voltage release: approximately 70 percent of nominal voltage
  • Power requirement: filtered or regulated DC (pulsating DC requires 1000 uF capacitor)
  • Mounting type: circuit board only
  • Certifications: ANSI/UL 294, CSFM
  • Code compliance: NFPA 101, BOCA, UBC, SBC, National Building Code of Canada
  • UL evaluation: evaluated for use in EXD-1 and EXD-1F FWAX systems